PET-70216/ET-7026 User Manual, version 1.0.1 beta1, Page: 14
Copyright © 2009 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]om
Power-up and Safe Value
Yes
Open Wire for Current Output
4 mA ~ 20 mA
Digital Input
Input Type
2 (Dry + Wet)
Dry Contact
On Voltage Level
Close to GND
(Source)
Off Voltage Level
Open
Effective Distance
for Dry Contact
500M Max.
Wet Contact
On Voltage Level
+1 V
DC
Max.
(Sink/Source)
Off Voltage Level
+3.5 V
DC
~ +30 V
DC
Counter
Channels
2
Max. Counts
32-bit (4294967295)
Max. Input
Frequency
100 Hz
Min. Pulse Width
5 ms
Digital Output
Output Channels
2 (Sink)
Output Type
Isolated Open Collector
Max. Load Current
700 mA/Channel
Load Voltage
+5 V
DC
~ +50 V
DC
External Power Reversed Protection
and Short Circuit Protection
Yes
Over-Temperature Protection
Yes, 150 ^ C
Current Limited Protection
1.1 A