Installation and Operating Instructions
SDC 306 1316BED036-11B-E Date 06/09
- 12 -
6.2 Attachment of temperature sensor
The SDC 306 devices work with precise platinum temperature sensors of type PT1000.
Between 2 and 5 sensors are required, depending on the scope of function.
Installation/wiring of temperature sensor:
Install the sensors at the requisite places
on the collector and the storage cylinder.
In so doing, ensure good temperature
transmission and, if necessary, use a
thermally conductive paste.
The cables of the temperature sensors
can be extended. For lengths up to 15 m,
a cross-section of 2 x 0.5 mm² is
required; for lengths up to 50 m, a cross-
section of 2 x 0.75 mm² is necessary. In
the case of long connections (collector),
shielded extension cables must be used.
Do not attach the shield on the sensor
side; instead cut it to length and insulate
it.
The temperature sensors are connected
in accordance with the system diagram.
In the case of temperature sensors, there
is no need to observe the polarity of the
two wires.
To protect the collector sensor within the
control unit, the use of a lightning
protection device (accessories) is
recommended.
Sensor wiring must be laid separately
from 230 V wires.
Prior to switching on or commissioning, you must ensure that the cover is
closed properly such that you feel and hear it click into position on both
sides.